Supply ventilation fan electric explosion-proof

5/17/2012 6:24:12 PM

Ventilation fan electric explosion-proof(hereinafter referred to as ventilation fans), made its explosion-proof performance and GB3836.2-83 explosive environment with the provisions of the explosion-proof electrical equipment explosion-proof electrical equipment "d" "flameproof .

The proof mark d Ⅱ CT4 applicable to Class Ⅱ, A, B, level of T1, the T2, T3,, T4, to form a combustible gas with air to form explosive environment. Ventilation fans have explosion-proof, reliable performance, large air volume, low noise, low power consumption advantages. And has national legal proof testing unit safety inspection, and has made explosion-proof certificate.

ventilation fans installation and use

1. first check the framework, the blades with or without deformation, the fan rotation is flexible, with or without friction phenomenon. Check all fasteners are complete, tighten, should be explosion-proof certificate number.

 

2. line voltage and the motor rated voltage match.

3. with 500V megger check the motor insulation resistance, its resistance value is less than 50MΩ, the application of the drying method or short-circuit current method for drying, so that the insulation resistance greater than 5 MΩ.

4. ventilation fans must be equipped with a small explosion-proof switch the power switch or ordinary switch installed in outdoor non-explosive dangerous place.

5. then the power of cable diameter should be consistent with the ring, tighten the compression nut should ensure that the seals and cable outlet between Tsui gap, otherwise it will lose the explosion-proof performance.

6. the assembly should ensure explosion-proof gap is less than 0.2mm, replace the motor bearings, grease, grease grades ZG-2H compound calcium-based Run.

7. the non-terminal part of the explosion-proof motor is not disassemble, wiring, open the cover of the terminal room, penetration leads to terminals connected, covered with a lid tighten the screw so that the explosion-proof surface gap is less than 0.2mm, then tighten the outlet, so that leads can not traverse. Note: When installing, pay attention to explosion-proof surface, flameproof surface of the assembly shall be painted in the 204-1 anti-rust grease. All explosion-proof surface shall not damage or corrosion, or they will lose proof performance, if any damage or corrosion phenomena according to the "explosion-proof electrical equipment explosion-proof surface defects processing rule" to repair.

8. using ventilation fans should always clean up dust and other accumulations in motor, so as not to affect the heat.

9. re-use of long-term unused ventilation fans shall be specified and then check it again, after appropriate before use.